Flexible Modular Redundancy
Single design
- The ET 200S I/O system
 |
The
ET 200S is used for distributed expansion of the SIMATIC
safety controllers via PROFIBUS.
An ET 200S station can contain both
failsafe and standard input and output modules. Compliance with
SIL 3 is attained through the use of a type
PM-E 24 V DC/120/230 V AC power module.
|
Product overview:
Characteristic: bit modular I/O module with up to 8 channels
per modul.
| Module |
Properties |
| 4/8 F-DI DC 24 V
|
| - |
4 x two-channel inputs
SIL 3/Category 4 or |
| - |
8 x one-channel inputs SIL 2 |
|
| 4 F-DO DC 24
V/2 A |
| - |
4 output channels P-M
switching SIL 3/Category 4 |
|
PM-E F DC 24 V
(P-M switching) |
Fail-safe infeed module
| - |
2 semiconductor output
channels, SIL 3/Category 4 |
| - |
1 safety relay output 10 A for SIL
3/Category 4 |
| - |
Fail-safe disabling
of standard DO up to Category 3 |
|
PM-E F DC 24 V
(P-P switching) |
Fail-safe infeed module
| - |
1 safety relay output 10 A for SIL
3/Category 4 |
| - |
Fail-safe disabling
of standard DO up to Category 3 |
|
| PM-E |
| - |
Standard infeed module
for I/O modules |
|
The IM 151-1 High Feature interface module must be used
to configure distributed safe stations.
|